Modbus Type
Modbus TCP
For a related example, see Creating Modbus TCP WCI.
Item | Description |
---|---|
Company Logo | Attach a logo image of the company manufacturing the Worcell Item. |
IP Address | Assign the access address of the Modbus Master to connect. |
Port Number | Assign the port of the Modbus Master to connect. |
Slave Id | Set the Slave Id. |
Modbus RTU
Item | Description |
---|---|
Company Logo | Attach a logo image of the company manufacturing the Worcell Item. |
Slave ID | Set the Slave Id. |
Port Type | Select the Serial Port Type. It searches and displays the device list connected from the top controller. |
Baud Rate | Set the Baud Rate. |
Bit Size | Set the Bit Size. |
Parity Bit | Set the Parity Bit. |
Stop Bit | Set the Stop Bit. |
Output/Input Signal
Output Signal
Item | Description |
---|---|
Write Signal Name | Set the name of the signal to add. Only English characters and "_" symbols can be entered, and the maximum length is 20 characters. |
Signal Type | Select the signal type of Modbus.
- Write Coil, Write Register, Write Multiple Coils, Write Multiple Registers |
Signal Address Index | Enter the address of the Modbus signal. |
Signal Initial Value | Enter the default value of the signal. |
Custom Data | Use it when delivering multiple values. Input in the following format when the signal type is Write Multiple Coils or Write Multiple Registers.
ex> 1,0,1,0,1 |
Lock Field | Check the item to set so that it cannot be edited or deleted in the top controller. |
Input Signal
Item | Description |
---|---|
Read Signal Name | Set the name of the signal to add. Only English characters and "_" symbols can be entered, and the maximum length is 20 characters. |
Signal Type | Select the signal type of Modbus.
- Read Coil, Read Register |
Signal Address Index | Enter the address of the Modbus signal. |
Custom Data | This menu is deactivated. |
Lock Field | Check the item to set so that it cannot be edited or deleted in the top controller. |